Heatproof
Home / system #310

Daikin Altherma 3

Telford · Detached · 130 m² · 2012 or newer · 4 kW · radiators · installed by Octopus Energy Services

Last 30 days

721 hourly rows · MID-class heat meter present: no
3.79efficiency (COP) over 721 hours, from the heat meter
better than 59% of the metered fleet in January 2026
Electricity used
188 kWh
Heat delivered
712 kWh (heat meter)
Estimate without heat meter
flow sensor 3.84 · temperature model 4.22
Mean outdoor temperature
11.0 °C · 184 space-heating hours · cooling 1 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
38.9 °C (curve slope -0.46 per K)
Flow − return while heating
4.6 K
House needs at −3 °C
4.1 kW (unit rated 4 kW) · fit r² 0.08
Hot water
32% of electricity, COP 3.29
warningHot water uses 32% of electricity at COP 3.29
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day05102026-10-08: 5.5 kWh, outside 11.7 °C2026-10-09: 3.6 kWh, outside 14.6 °C2026-10-10: 6.4 kWh, outside 12.4 °C2026-10-11: 3.3 kWh, outside 11.4 °C2026-10-12: 4.1 kWh, outside 14.3 °C2026-10-13: 2.7 kWh, outside 15.4 °C2026-10-14: 5.4 kWh, outside 13.1 °C2026-10-15: 2.5 kWh, outside 16 °C2026-10-16: 3.5 kWh, outside 12.7 °C2026-10-17: 9.3 kWh, outside 9.5 °C2026-10-18: 5.1 kWh, outside 8.7 °C2026-10-19: 5.1 kWh, outside 10.6 °C2026-10-20: 7.4 kWh, outside 10 °C2026-10-21: 7.7 kWh, outside 8.7 °C2026-10-22: 8.1 kWh, outside 8.9 °C2026-10-23: 9.6 kWh, outside 8.6 °C2026-10-24: 10.3 kWh, outside 9 °C2026-10-25: 4.8 kWh, outside 10.4 °C2026-10-26: 6 kWh, outside 11.2 °C2026-10-27: 3.9 kWh, outside 12.6 °C2026-10-28: 4.5 kWh, outside 12.5 °C2026-10-29: 5 kWh, outside 12.9 °C2026-10-30: 4.8 kWh, outside 12.2 °C2026-10-31: 9 kWh, outside 10.3 °C2026-11-01: 5 kWh, outside 9.2 °C2026-11-02: 8.1 kWh, outside 8.6 °C2026-11-03: 8.2 kWh, outside 8.8 °C2026-11-04: 7.6 kWh, outside 9.4 °C2026-11-05: 8.3 kWh, outside 8.3 °C2026-11-06: 10.3 kWh, outside 8.9 °C2026-11-07: 3.4 kWh, outside 7.7 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 3.922026-10-09: COP 4.012026-10-10: COP 3.682026-10-11: COP 42026-10-12: COP 4.472026-10-13: COP 3.32026-10-14: COP 3.842026-10-15: COP 3.932026-10-16: COP 3.612026-10-17: COP 3.432026-10-18: COP 3.692026-10-19: COP 3.872026-10-20: COP 3.662026-10-21: COP 3.882026-10-22: COP 3.642026-10-23: COP 4.022026-10-24: COP 3.752026-10-25: COP 4.112026-10-26: COP 3.82026-10-27: COP 3.532026-10-28: COP 4.252026-10-29: COP 4.012026-10-30: COP 3.942026-10-31: COP 3.652026-11-01: COP 3.982026-11-02: COP 3.472026-11-03: COP 3.792026-11-04: COP 3.742026-11-05: COP 3.432026-11-06: COP 3.712026-11-07: COP 3.8110-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050603579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.