Heatproof
Home / system #310

Daikin Altherma 3

Telford · Detached · 130 m² · 2012 or newer · 4 kW · radiators · installed by Octopus Energy Services

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: no
3.46efficiency (COP) over 721 hours, from the heat meter
better than 36% of the metered fleet in January 2026
Electricity used
414 kWh
Heat delivered
1430 kWh (heat meter)
Estimate without heat meter
flow sensor 3.56 · temperature model 3.33
Mean outdoor temperature
5.6 °C · 394 space-heating hours · cooling 14 kWh removed (3 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
38.2 °C (curve slope -0.13 per K)
Flow − return while heating
5.5 K
House needs at −3 °C
3.8 kW (unit rated 4 kW) · fit r² 0.04
Hot water
12% of electricity, COP 2.86
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
valueReaching the fleet’s January median (3.69) would have saved about £7 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day013262026-01-05: 25.8 kWh, outside -0.1 °C2026-01-06: 19.9 kWh, outside 3.1 °C2026-01-07: 14.6 kWh, outside 4.5 °C2026-01-08: 17.5 kWh, outside 2.9 °C2026-01-09: 19.5 kWh, outside 2.4 °C2026-01-10: 22.9 kWh, outside 1.8 °C2026-01-11: 15 kWh, outside 5.3 °C2026-01-12: 9.5 kWh, outside 9.4 °C2026-01-13: 9.1 kWh, outside 7.3 °C2026-01-14: 18.4 kWh, outside 3 °C2026-01-15: 12.9 kWh, outside 5.8 °C2026-01-16: 13.5 kWh, outside 6 °C2026-01-17: 11.7 kWh, outside 6.8 °C2026-01-18: 11.6 kWh, outside 5.9 °C2026-01-19: 10.2 kWh, outside 7.1 °C2026-01-20: 10.4 kWh, outside 8 °C2026-01-21: 11.3 kWh, outside 7.5 °C2026-01-22: 8.4 kWh, outside 8.3 °C2026-01-23: 11.7 kWh, outside 7 °C2026-01-24: 11.9 kWh, outside 7 °C2026-01-25: 10.8 kWh, outside 6.5 °C2026-01-26: 16.1 kWh, outside 4.2 °C2026-01-27: 12.8 kWh, outside 6.7 °C2026-01-28: 11.4 kWh, outside 6.2 °C2026-01-29: 15.3 kWh, outside 4.6 °C2026-01-30: 13.6 kWh, outside 5.9 °C2026-01-31: 12.7 kWh, outside 7.1 °C2026-02-01: 10 kWh, outside 7 °C2026-02-02: 10.7 kWh, outside 6.8 °C2026-02-03: 17.2 kWh, outside 3.5 °C2026-02-04: 0 kWh, outside 2 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 2.752026-01-06: COP 3.12026-01-07: COP 3.442026-01-08: COP 3.072026-01-09: COP 2.792026-01-10: COP 2.782026-01-11: COP 3.352026-01-12: COP 4.312026-01-13: COP 3.72026-01-14: COP 2.872026-01-15: COP 3.692026-01-16: COP 3.662026-01-17: COP 3.752026-01-18: COP 3.732026-01-19: COP 3.792026-01-20: COP 4.062026-01-21: COP 3.642026-01-22: COP 4.072026-01-23: COP 3.722026-01-24: COP 3.82026-01-25: COP 3.792026-01-26: COP 3.082026-01-27: COP 3.832026-01-28: COP 3.392026-01-29: COP 3.342026-01-30: COP 3.462026-01-31: COP 3.722026-02-01: COP 4.012026-02-02: COP 3.72026-02-03: COP 2.9701-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-3-11357911outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.