Heatproof
Home / system #310

Daikin Altherma 3

Telford · Detached · 130 m² · 2012 or newer · 4 kW · radiators · installed by Octopus Energy Services

Last 7 days

169 hourly rows · MID-class heat meter present: no
3.70efficiency (COP) over 169 hours, from the heat meter
better than 53% of the metered fleet in January 2026
Electricity used
59 kWh
Heat delivered
216 kWh (heat meter)
Estimate without heat meter
flow sensor 3.71 · temperature model 3.97
Mean outdoor temperature
8.9 °C · 61 space-heating hours · cooling 1 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
37.9 °C (curve slope -0.34 per K)
Flow − return while heating
4.5 K
House needs at −3 °C
4.7 kW (unit rated 4 kW) · fit r² 0.12
Hot water
26% of electricity, COP 3.16
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day05102026-10-31: 7.2 kWh, outside 9.7 °C2026-11-01: 5 kWh, outside 9.2 °C2026-11-02: 8.1 kWh, outside 8.6 °C2026-11-03: 8.2 kWh, outside 8.8 °C2026-11-04: 7.6 kWh, outside 9.4 °C2026-11-05: 8.3 kWh, outside 8.3 °C2026-11-06: 10.3 kWh, outside 8.9 °C2026-11-07: 4 kWh, outside 7.7 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.552026-11-01: COP 3.982026-11-02: COP 3.472026-11-03: COP 3.792026-11-04: COP 3.742026-11-05: COP 3.432026-11-06: COP 3.712026-11-07: COP 3.8610-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050603456789101112outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.