Heatproof
Home / system #421

Daikin Altherma 2

Horsham, West Sussex · Detached · 128 m² · 1983 to 2011 · 7 kW · radiators · installed by Octopus Energy Services

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: no
3.44efficiency (COP) over 721 hours, from the heat meter
better than 36% of the metered fleet in January 2026
Electricity used
580 kWh
Heat delivered
1999 kWh (heat meter)
Estimate without heat meter
flow sensor 3.58 · temperature model 3.48
Mean outdoor temperature
6.5 °C · 637 space-heating hours · cooling 0 kWh removed (1 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
39.2 °C (curve slope -0.54 per K)
Flow − return while heating
3.6 K
House needs at −3 °C
4.8 kW (unit rated 7 kW) · fit r² 0.51
Hot water
10% of electricity, COP 2.73
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
valueReaching the fleet’s January median (3.69) would have saved about £10 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day020402026-01-05: 39.5 kWh, outside -1.4 °C2026-01-06: 39.3 kWh, outside -0.9 °C2026-01-07: 26.3 kWh, outside 3.6 °C2026-01-08: 20.8 kWh, outside 4.9 °C2026-01-09: 28 kWh, outside 3.8 °C2026-01-10: 34.1 kWh, outside 1.3 °C2026-01-11: 26.1 kWh, outside 4.6 °C2026-01-12: 14.8 kWh, outside 10.7 °C2026-01-13: 11.6 kWh, outside 10.1 °C2026-01-14: 20 kWh, outside 6.1 °C2026-01-15: 14.6 kWh, outside 8.6 °C2026-01-16: 18.8 kWh, outside 6.9 °C2026-01-17: 14.2 kWh, outside 8.6 °C2026-01-18: 12.9 kWh, outside 9.2 °C2026-01-19: 11.6 kWh, outside 9.5 °C2026-01-20: 12.2 kWh, outside 8.9 °C2026-01-21: 14 kWh, outside 8.3 °C2026-01-22: 13.1 kWh, outside 8.9 °C2026-01-23: 14.7 kWh, outside 7.5 °C2026-01-24: 14.1 kWh, outside 7.8 °C2026-01-25: 15.3 kWh, outside 7.1 °C2026-01-26: 18.9 kWh, outside 6 °C2026-01-27: 14.9 kWh, outside 7.8 °C2026-01-28: 22.6 kWh, outside 4.8 °C2026-01-29: 25.2 kWh, outside 4 °C2026-01-30: 16.3 kWh, outside 8.3 °C2026-01-31: 14.7 kWh, outside 8.4 °C2026-02-01: 14.5 kWh, outside 8.3 °C2026-02-02: 16.4 kWh, outside 7 °C2026-02-03: 19.7 kWh, outside 5.4 °C2026-02-04: 2.3 kWh, outside 4.7 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 2.562026-01-06: COP 2.612026-01-07: COP 3.022026-01-08: COP 3.292026-01-09: COP 3.092026-01-10: COP 2.732026-01-11: COP 3.192026-01-12: COP 3.932026-01-13: COP 4.162026-01-14: COP 3.112026-01-15: COP 42026-01-16: COP 3.652026-01-17: COP 3.952026-01-18: COP 4.112026-01-19: COP 4.212026-01-20: COP 4.132026-01-21: COP 4.082026-01-22: COP 4.12026-01-23: COP 3.972026-01-24: COP 42026-01-25: COP 3.912026-01-26: COP 3.642026-01-27: COP 3.962026-01-28: COP 3.132026-01-29: COP 3.082026-01-30: COP 3.722026-01-31: COP 42026-02-01: COP 42026-02-02: COP 3.832026-02-03: COP 3.722026-02-04: COP 2.5401-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-8-5-21471013outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.