Home / system #445
Vaillant Arotherm+
Hackney, London · End-terrace · 82.1 m² · 1940 to 1982 · 3.5 kW · radiators · installed by Hilton Warm & Cool London
Last 30 days
721 hourly rows · MID-class heat meter present: yes
1.76efficiency (COP) over 721 hours, from the heat meter
better than 1% of the metered fleet in January 2026
better than 1% of the metered fleet in January 2026
- Electricity used
- 107 kWh
- Heat delivered
- 187 kWh (heat meter)
- Estimate without heat meter
- flow sensor 2.08 · temperature model 5.46
- Mean outdoor temperature
- 12.3 °C · 173 space-heating hours
- Flow temperature at 0 °C outside
- 23.5 °C (curve slope 0.61 per K)
- Flow − return while heating
- 2.0 K
- House needs at −3 °C
- 1.1 kW (unit rated 3.5 kW) · fit r² 0.03
- Hot water
- no hot-water flag in data
seriousWinter efficiency 1.76 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
warningOnly 2 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
infoUnit is rated 3.5 kW but the house needs about 1.1 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £14 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.