Heatproof
Home / system #445

Vaillant Arotherm+

Hackney, London · End-terrace · 82.1 m² · 1940 to 1982 · 3.5 kW · radiators · installed by Hilton Warm & Cool London

1–31 Dec 2025

745 hourly rows · MID-class heat meter present: yes
4.32efficiency (COP) over 745 hours, from the heat meter
better than 91% of the metered fleet in January 2026
Electricity used
189 kWh
Heat delivered
815 kWh (heat meter)
Estimate without heat meter
flow sensor 4.38 · temperature model 4.35
Mean outdoor temperature
8.4 °C · 252 space-heating hours · cooling 10 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
34.8 °C (curve slope -0.21 per K)
Flow − return while heating
3.4 K
House needs at −3 °C
4.3 kW (unit rated 3.5 kW) · fit r² 0.11
Hot water
no hot-water flag in data
warningUnit is rated 3.5 kW but the house needs about 4.3 kW at −3 °C
Expect backup heater use on the coldest days. Improve insulation or draught-proofing before adding capacity.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day05102025-12-01: 6.1 kWh, outside 10.4 °C2025-12-02: 4.9 kWh, outside 9.2 °C2025-12-03: 7.9 kWh, outside 7.3 °C2025-12-04: 5.6 kWh, outside 7.2 °C2025-12-05: 8.4 kWh, outside 5.7 °C2025-12-06: 4.7 kWh, outside 10.9 °C2025-12-07: 4.6 kWh, outside 11.2 °C2025-12-08: 5.7 kWh, outside 12.3 °C2025-12-09: 4.2 kWh, outside 13.3 °C2025-12-10: 3.8 kWh, outside 11.5 °C2025-12-11: 4.4 kWh, outside 9.9 °C2025-12-12: 4 kWh, outside 10.7 °C2025-12-13: 4.8 kWh, outside 7.1 °C2025-12-14: 5.1 kWh, outside 8.8 °C2025-12-15: 4.5 kWh, outside 11.1 °C2025-12-16: 5.4 kWh, outside 10.3 °C2025-12-17: 5.9 kWh, outside 6.6 °C2025-12-18: 4.9 kWh, outside 11.3 °C2025-12-19: 5.5 kWh, outside 9.1 °C2025-12-20: 6.4 kWh, outside 7.3 °C2025-12-21: 5.6 kWh, outside 9.7 °C2025-12-22: 4.9 kWh, outside 10 °C2025-12-23: 6 kWh, outside 7.7 °C2025-12-24: 7.3 kWh, outside 5.6 °C2025-12-25: 8.6 kWh, outside 4.4 °C2025-12-26: 8.5 kWh, outside 5.1 °C2025-12-27: 9.7 kWh, outside 5.8 °C2025-12-28: 7.2 kWh, outside 7.2 °C2025-12-29: 7.8 kWh, outside 6.1 °C2025-12-30: 8.6 kWh, outside 5.2 °C2025-12-31: 9.7 kWh, outside 1.7 °C2026-01-01: 0.1 kWh, outside 0.1 °Cdaily COP (heat ÷ electricity)1352025-12-01: COP 4.142025-12-02: COP 4.932025-12-03: COP 4.272025-12-04: COP 4.452025-12-05: COP 3.942025-12-06: COP 5.12025-12-07: COP 5.082025-12-08: COP 4.112025-12-09: COP 4.722025-12-10: COP 5.282025-12-11: COP 4.962025-12-12: COP 4.732025-12-13: COP 4.792025-12-14: COP 4.632025-12-15: COP 4.962025-12-16: COP 4.012025-12-17: COP 4.462025-12-18: COP 4.982025-12-19: COP 4.662025-12-20: COP 4.362025-12-21: COP 4.772025-12-22: COP 4.82025-12-23: COP 4.052025-12-24: COP 3.972025-12-25: COP 3.482025-12-26: COP 3.632025-12-27: COP 3.782025-12-28: COP 4.032025-12-29: COP 3.842025-12-30: COP 3.22025-12-31: COP 3.2512-0112-0512-0912-1312-1712-2112-2512-29
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506070-113579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.