Heatproof
Home / system #445

Vaillant Arotherm+

Hackney, London · End-terrace · 82.1 m² · 1940 to 1982 · 3.5 kW · radiators · installed by Hilton Warm & Cool London

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: yes
3.72efficiency (COP) over 721 hours, from the heat meter
better than 56% of the metered fleet in January 2026
Electricity used
308 kWh
Heat delivered
1146 kWh (heat meter)
Estimate without heat meter
flow sensor 3.74 · temperature model 3.54
Mean outdoor temperature
6.6 °C · 334 space-heating hours · cooling 13 kWh removed (1 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
39.2 °C (curve slope -0.35 per K)
Flow − return while heating
4.0 K
House needs at −3 °C
2.6 kW (unit rated 3.5 kW) · fit r² 0.09
Hot water
no hot-water flag in data
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day014282026-01-05: 14.6 kWh, outside 0.1 °C2026-01-06: 12.7 kWh, outside 0 °C2026-01-07: 28 kWh, outside 4 °C2026-01-08: 15.7 kWh, outside 4.3 °C2026-01-09: 15.2 kWh, outside 4.7 °C2026-01-10: 17.1 kWh, outside 2.4 °C2026-01-11: 16.9 kWh, outside 4.5 °C2026-01-12: 7.4 kWh, outside 10.4 °C2026-01-13: 7.6 kWh, outside 9.6 °C2026-01-14: 10.1 kWh, outside 5.8 °C2026-01-15: 7.4 kWh, outside 8.9 °C2026-01-16: 8.7 kWh, outside 7.3 °C2026-01-17: 8 kWh, outside 8.8 °C2026-01-18: 7.6 kWh, outside 9.1 °C2026-01-19: 7.4 kWh, outside 9.4 °C2026-01-20: 8.3 kWh, outside 9.3 °C2026-01-21: 7.7 kWh, outside 8.4 °C2026-01-22: 7.6 kWh, outside 8.9 °C2026-01-23: 9.1 kWh, outside 8 °C2026-01-24: 8.7 kWh, outside 7.7 °C2026-01-25: 7.2 kWh, outside 7.1 °C2026-01-26: 9.5 kWh, outside 5.6 °C2026-01-27: 9.1 kWh, outside 7.6 °C2026-01-28: 9.3 kWh, outside 5.9 °C2026-01-29: 9.5 kWh, outside 4.5 °C2026-01-30: 7.8 kWh, outside 7.6 °C2026-01-31: 7.2 kWh, outside 8.2 °C2026-02-01: 7.1 kWh, outside 8.1 °C2026-02-02: 7.8 kWh, outside 7.7 °C2026-02-03: 8.8 kWh, outside 5.1 °C2026-02-04: 0 kWh, outside 4.4 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 2.722026-01-06: COP 2.682026-01-07: COP 3.182026-01-08: COP 3.912026-01-09: COP 3.772026-01-10: COP 3.322026-01-11: COP 3.392026-01-12: COP 4.622026-01-13: COP 3.942026-01-14: COP 3.672026-01-15: COP 4.252026-01-16: COP 3.832026-01-17: COP 4.162026-01-18: COP 4.262026-01-19: COP 4.342026-01-20: COP 3.912026-01-21: COP 4.312026-01-22: COP 4.312026-01-23: COP 3.972026-01-24: COP 3.982026-01-25: COP 4.032026-01-26: COP 3.322026-01-27: COP 3.492026-01-28: COP 3.382026-01-29: COP 3.32026-01-30: COP 3.822026-01-31: COP 4.182026-02-01: COP 4.252026-02-02: COP 4.072026-02-03: COP 3.1601-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506070-5-3-1135791113outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.