Samsung Gen 6

Carlby, STAMFORD · Detached · 184 m² · 1940 to 1982 · 12 kW · radiators · installed by Forerunner (Electronic) Ltd

Last 30 days

721 hourly rows · MID-class heat meter present: no
2.80efficiency (COP) over 721 hours, from the heat meter
better than 5% of the metered fleet in January 2026
Electricity used
316 kWh
Heat delivered
883 kWh (heat meter)
Estimate without heat meter
flow sensor 2.65 · temperature model 3.50
Mean outdoor temperature
10.8 °C · 214 space-heating hours · cooling 0 kWh removed (0 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
51.7 °C (curve slope -1.02 per K)
Flow − return while heating
3.6 K
House needs at −3 °C
5.8 kW (unit rated 12 kW) · fit r² 0.02
Hot water
no hot-water flag in data
seriousWinter efficiency 2.8 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
seriousFlow temperature runs at about 51.7 °C when it is 0 °C outside
Lower the heating curve in steps of 2 °C and check rooms still reach target. Every 1 °C lower typically saves 2–3% electricity.
infoUnit is rated 12 kW but the house needs about 5.8 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Outside temperature error”
valueReaching the fleet’s January median (3.69) would have saved about £19 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day011222026-10-08: 13.8 kWh, outside 11.2 °C2026-10-09: 4.1 kWh, outside 14.3 °C2026-10-10: 12.9 kWh, outside 10.7 °C2026-10-11: 3.3 kWh, outside 10.3 °C2026-10-12: 3.6 kWh, outside 12.3 °C2026-10-13: 0.2 kWh, outside 16 °C2026-10-14: 0.8 kWh, outside 12.9 °C2026-10-15: 0.2 kWh, outside 16.7 °C2026-10-16: 8.3 kWh, outside 12 °C2026-10-17: 7.3 kWh, outside 9.2 °C2026-10-18: 9.1 kWh, outside 10.2 °C2026-10-19: 2.9 kWh, outside 11.8 °C2026-10-20: 7.6 kWh, outside 11.8 °C2026-10-21: 14.9 kWh, outside 8.9 °C2026-10-22: 16.6 kWh, outside 8.9 °C2026-10-23: 15.2 kWh, outside 10.1 °C2026-10-24: 18.6 kWh, outside 9.3 °C2026-10-25: 19.6 kWh, outside 10.3 °C2026-10-26: 14.3 kWh, outside 11.1 °C2026-10-27: 5.7 kWh, outside 13.4 °C2026-10-28: 7.6 kWh, outside 10.6 °C2026-10-29: 9.8 kWh, outside 11 °C2026-10-30: 12.5 kWh, outside 9.4 °C2026-10-31: 13.3 kWh, outside 9.1 °C2026-11-01: 12.9 kWh, outside 8.9 °C2026-11-02: 14.7 kWh, outside 8.7 °C2026-11-03: 15.9 kWh, outside 9.1 °C2026-11-04: 20.5 kWh, outside 9.4 °C2026-11-05: 21.6 kWh, outside 8.9 °C2026-11-06: 8.2 kWh, outside 9.1 °C2026-11-07: 0.1 kWh, outside 7.2 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 2.752026-10-09: COP 3.312026-10-10: COP 3.052026-10-11: COP 2.522026-10-12: COP 2.442026-10-14: COP 0.222026-10-16: COP 3.122026-10-17: COP 2.392026-10-18: COP 2.762026-10-19: COP 2.712026-10-20: COP 2.872026-10-21: COP 2.622026-10-22: COP 2.732026-10-23: COP 2.522026-10-24: COP 2.722026-10-25: COP 2.672026-10-26: COP 2.742026-10-27: COP 2.572026-10-28: COP 2.892026-10-29: COP 3.052026-10-30: COP 3.142026-10-31: COP 3.072026-11-01: COP 3.072026-11-02: COP 32026-11-03: COP 2.942026-11-04: COP 2.672026-11-05: COP 2.662026-11-06: COP 2.6910-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050605678910111213141516outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.