Heatproof
Home / system #70

Samsung Gen 6

Carlby, STAMFORD · Detached · 184 m² · 1940 to 1982 · 12 kW · radiators · installed by Forerunner (Electronic) Ltd

Last 7 days

169 hourly rows · MID-class heat meter present: no
2.86efficiency (COP) over 169 hours, from the heat meter
better than 6% of the metered fleet in January 2026
Electricity used
107 kWh
Heat delivered
306 kWh (heat meter)
Estimate without heat meter
flow sensor 2.80 · temperature model 3.35
Mean outdoor temperature
8.9 °C · 75 space-heating hours
Flow temperature at 0 °C outside
35.8 °C (curve slope 0.61 per K)
Flow − return while heating
3.6 K
House needs at −3 °C
2.4 kW (unit rated 12 kW) · fit r² 0.01
Hot water
no hot-water flag in data
seriousWinter efficiency 2.86 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
infoUnit is rated 12 kW but the house needs about 2.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Outside temperature error”
valueReaching the fleet’s January median (3.69) would have saved about £6 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day011222026-10-31: 13.2 kWh, outside 9.3 °C2026-11-01: 12.9 kWh, outside 8.9 °C2026-11-02: 14.7 kWh, outside 8.7 °C2026-11-03: 15.9 kWh, outside 9.1 °C2026-11-04: 20.5 kWh, outside 9.4 °C2026-11-05: 21.6 kWh, outside 8.9 °C2026-11-06: 8.2 kWh, outside 9.1 °C2026-11-07: 0.1 kWh, outside 7.2 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.092026-11-01: COP 3.072026-11-02: COP 32026-11-03: COP 2.942026-11-04: COP 2.672026-11-05: COP 2.662026-11-06: COP 2.6910-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050605678910111213outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.