Samsung Gen 6
Carlby, STAMFORD · Detached · 184 m² · 1940 to 1982 · 12 kW · radiators · installed by Forerunner (Electronic) Ltd
Last 7 days
169 hourly rows · MID-class heat meter present: no
2.86efficiency (COP) over 169 hours, from the heat meter
better than 6% of the metered fleet in January 2026
better than 6% of the metered fleet in January 2026
- Electricity used
- 107 kWh
- Heat delivered
- 306 kWh (heat meter)
- Estimate without heat meter
- flow sensor 2.80 · temperature model 3.35
- Mean outdoor temperature
- 8.9 °C · 75 space-heating hours
- Flow temperature at 0 °C outside
- 35.8 °C (curve slope 0.61 per K)
- Flow − return while heating
- 3.6 K
- House needs at −3 °C
- 2.4 kW (unit rated 12 kW) · fit r² 0.01
- Hot water
- no hot-water flag in data
seriousWinter efficiency 2.86 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
infoUnit is rated 12 kW but the house needs about 2.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Outside temperature error”
valueReaching the fleet’s January median (3.69) would have saved about £6 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.