Home / system #88
Stiebel Eltron WPL25-AS
Lichfield, UK · Detached · 202 m² · 1940 to 1982 · 12.5 kW · underfloor · installed by Niche Energy Systems Ltd
5 Jan – 4 Feb 2026 (winter reference)
368 hourly rows · MID-class heat meter present: no
2.75efficiency (COP) over 368 hours, from the heat meter
better than 3% of the metered fleet in January 2026
better than 3% of the metered fleet in January 2026
- Electricity used
- 841 kWh
- Heat delivered
- 2310 kWh (heat meter)
- Estimate without heat meter
- flow sensor 2.76 · temperature model 3.60
- Mean outdoor temperature
- 3.6 °C · 356 space-heating hours
- Flow temperature at 0 °C outside
- 37.4 °C (curve slope -0.65 per K)
- Flow − return while heating
- 5.0 K
- House needs at −3 °C
- 8.8 kW (unit rated 12.5 kW) · fit r² 0.11
- Hot water
- no hot-water flag in data
seriousWinter efficiency 2.75 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
valueReaching the fleet’s January median (3.69) would have saved about £54 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.