721 hourly rows · MID-class heat meter present: yes
3.99efficiency (COP) over 721 hours, from the heat meter better than 76% of the metered fleet in January 2026
Electricity used
458 kWh
Heat delivered
1826 kWh (heat meter)
Estimate without heat meter
flow sensor 3.95 · temperature model 4.26
Mean outdoor temperature
11.6 °C · 357 space-heating hours
Flow temperature at 0 °C outside
40.5 °C (curve slope -0.64 per K)
Flow − return while heating
2.1 K
House needs at −3 °C
7.6 kW (unit rated 12 kW) · fit r² 0.15
Hot water
21% of electricity, COP 3.42
warningOnly 2.1 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.