Heatproof
Home / system #968

Samsung Gen 7

Surbiton, Surrey · Detached · 200 m² · 1900 to 1939 · 12 kW · underfloor · installed by Samso Energy

Last 7 days

169 hourly rows · MID-class heat meter present: yes
3.98efficiency (COP) over 169 hours, from the heat meter
better than 74% of the metered fleet in January 2026
Electricity used
141 kWh
Heat delivered
562 kWh (heat meter)
Estimate without heat meter
flow sensor 3.86 · temperature model 4.01
Mean outdoor temperature
9.2 °C · 123 space-heating hours
Flow temperature at 0 °C outside
43.3 °C (curve slope -0.96 per K)
Flow − return while heating
2.2 K
House needs at −3 °C
7.4 kW (unit rated 12 kW) · fit r² 0.09
Hot water
12% of electricity, COP 3.13
warningOnly 2.2 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day012242026-10-31: 6.2 kWh, outside 11.6 °C2026-11-01: 17.3 kWh, outside 8.8 °C2026-11-02: 19.3 kWh, outside 9.8 °C2026-11-03: 18.3 kWh, outside 9.9 °C2026-11-04: 23.8 kWh, outside 9.5 °C2026-11-05: 21.8 kWh, outside 9.2 °C2026-11-06: 22.9 kWh, outside 8.3 °C2026-11-07: 11.4 kWh, outside 4.5 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.712026-11-01: COP 4.222026-11-02: COP 4.172026-11-03: COP 4.082026-11-04: COP 4.212026-11-05: COP 4.042026-11-06: COP 3.692026-11-07: COP 3.310-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506034567891011121314outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.