Home / system #167

Nibe F2050

Cadross, Dumbarton · Detached · 123 m² · Pre-1900 · 10 kW · radiators · installed by Renewable Heat

Last 7 days

169 hourly rows · MID-class heat meter present: yes
4.73efficiency (COP) over 169 hours, from the heat meter
better than 97% of the metered fleet in January 2026
Electricity used
92 kWh
Heat delivered
437 kWh (heat meter)
Estimate without heat meter
flow sensor 4.78 · temperature model 4.10
Mean outdoor temperature
8.2 °C · 160 space-heating hours
Flow temperature at 0 °C outside
38.4 °C (curve slope -0.65 per K)
Flow − return while heating
2.6 K
House needs at −3 °C
4.5 kW (unit rated 10 kW) · fit r² 0.32
Hot water
no hot-water flag in data
warningOnly 2.6 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
infoUnit is rated 10 kW but the house needs about 4.5 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Unchecked primary circ pump flow rate change without visible pump power change”

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day09182026-10-31: 3.8 kWh, outside 12.2 °C2026-11-01: 11.3 kWh, outside 9.1 °C2026-11-02: 18.1 kWh, outside 5.2 °C2026-11-03: 12.8 kWh, outside 7.9 °C2026-11-04: 11.6 kWh, outside 7.2 °C2026-11-05: 13.6 kWh, outside 7.7 °C2026-11-06: 14.4 kWh, outside 9.2 °C2026-11-07: 6.8 kWh, outside 8.3 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 5.472026-11-01: COP 4.762026-11-02: COP 4.062026-11-03: COP 4.972026-11-04: COP 4.992026-11-05: COP 4.942026-11-06: COP 4.982026-11-07: COP 4.2410-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-113579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.