744 hourly rows · MID-class heat meter present: yes
3.88efficiency (COP) over 744 hours, from the heat meter better than 65% of the metered fleet in January 2026
Electricity used
547 kWh
Heat delivered
2120 kWh (heat meter)
Estimate without heat meter
flow sensor – · temperature model 3.59
Mean outdoor temperature
7.2 °C · 464 space-heating hours
Flow temperature at 0 °C outside
36.1 °C (curve slope 0.02 per K)
Flow − return while heating
5.8 K
House needs at −3 °C
4.6 kW (unit rated 11.2 kW) · fit r² 0.01
Hot water
7% of electricity, COP 3.41
infoUnit is rated 11.2 kW but the house needs about 4.6 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Defrost energy not included due to mitsubishi heat meter integration limitation.”
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.