Heatproof
Home / system #1

Mitsubishi Ecodan

Selby, Yorkshire · Detached · 134 m² · 1940 to 1982 · 11.2 kW · radiators · installed by Green Building Renewables

Last 7 days

160 hourly rows · MID-class heat meter present: yes
4.46efficiency (COP) over 160 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
87 kWh
Heat delivered
390 kWh (heat meter)
Estimate without heat meter
flow sensor – · temperature model 4.12
Mean outdoor temperature
9.2 °C · 68 space-heating hours
Flow temperature at 0 °C outside
31.8 °C (curve slope 0.30 per K)
Flow − return while heating
4.1 K
House needs at −3 °C
3.4 kW (unit rated 11.2 kW) · fit r² 0.02
Hot water
21% of electricity, COP 4.13
infoUnit is rated 11.2 kW but the house needs about 3.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Defrost energy not included due to mitsubishi heat meter integration limitation.”

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day09172026-10-31: 6.6 kWh, outside 9.3 °C2026-11-01: 17 kWh, outside 6.8 °C2026-11-02: 14.3 kWh, outside 8.3 °C2026-11-03: 12.2 kWh, outside 9.9 °C2026-11-04: 10.4 kWh, outside 10.2 °C2026-11-05: 14.1 kWh, outside 10.2 °C2026-11-06: 12.6 kWh, outside 10 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 4.612026-11-01: COP 4.162026-11-02: COP 4.372026-11-03: COP 4.672026-11-04: COP 4.742026-11-05: COP 4.532026-11-06: COP 4.4110-3111-0111-0211-0311-0411-0511-06
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060135791113outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.