Home / system #1
Mitsubishi Ecodan
Selby, Yorkshire · Detached · 134 m² · 1940 to 1982 · 11.2 kW · radiators · installed by Green Building Renewables
Last 7 days
160 hourly rows · MID-class heat meter present: yes
4.46efficiency (COP) over 160 hours, from the heat meter
better than 92% of the metered fleet in January 2026
better than 92% of the metered fleet in January 2026
- Electricity used
- 87 kWh
- Heat delivered
- 390 kWh (heat meter)
- Estimate without heat meter
- flow sensor – · temperature model 4.12
- Mean outdoor temperature
- 9.2 °C · 68 space-heating hours
- Flow temperature at 0 °C outside
- 31.8 °C (curve slope 0.30 per K)
- Flow − return while heating
- 4.1 K
- House needs at −3 °C
- 3.4 kW (unit rated 11.2 kW) · fit r² 0.02
- Hot water
- 21% of electricity, COP 4.13
infoUnit is rated 11.2 kW but the house needs about 3.4 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Defrost energy not included due to mitsubishi heat meter integration limitation.”
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.