721 hourly rows · MID-class heat meter present: yes
3.53efficiency (COP) over 721 hours, from the heat meter better than 38% of the metered fleet in January 2026
Electricity used
739 kWh
Heat delivered
2612 kWh (heat meter)
Estimate without heat meter
flow sensor – · temperature model 3.26
Mean outdoor temperature
4.6 °C · 554 space-heating hours
Flow temperature at 0 °C outside
37.9 °C (curve slope -0.30 per K)
Flow − return while heating
5.9 K
House needs at −3 °C
5.0 kW (unit rated 11.2 kW) · fit r² 0.03
Hot water
7% of electricity, COP 3.24
infoUnit is rated 11.2 kW but the house needs about 5 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “Defrost energy not included due to mitsubishi heat meter integration limitation.”
valueReaching the fleet’s January median (3.69) would have saved about £8 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.