745 hourly rows · MID-class heat meter present: yes
4.05efficiency (COP) over 745 hours, from the heat meter better than 80% of the metered fleet in January 2026
Electricity used
703 kWh
Heat delivered
2849 kWh (heat meter)
Estimate without heat meter
flow sensor 2.54 · temperature model 3.79
Mean outdoor temperature
7.6 °C · 478 space-heating hours
Flow temperature at 0 °C outside
43.8 °C (curve slope -0.58 per K)
Flow − return while heating
5.5 K
House needs at −3 °C
5.8 kW (unit rated 12 kW) · fit r² 0.11
Hot water
53% of electricity, COP 3.41
warningHot water uses 53% of electricity at COP 3.41
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 12 kW but the house needs about 5.8 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
noteOwner’s note on the source site: “0W standby power review required”
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.