721 hourly rows · MID-class heat meter present: no
3.54efficiency (COP) over 721 hours, from the heat meter better than 38% of the metered fleet in January 2026
Electricity used
1065 kWh
Heat delivered
3775 kWh (heat meter)
Estimate without heat meter
flow sensor 3.51 · temperature model 2.97
Mean outdoor temperature
3.0 °C · 543 space-heating hours
Flow temperature at 0 °C outside
41.0 °C (curve slope -0.67 per K)
Flow − return while heating
4.1 K
House needs at −3 °C
7.0 kW (unit rated 9 kW) · fit r² 0.31
Hot water
26% of electricity, COP 3.29
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
valueReaching the fleet’s January median (3.69) would have saved about £11 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
Daily COP needs a heat meter; days without one show electricity only.
The installed heating curve
one heating hourfitted curve50 °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.