Heatproof
Home / system #293

Daikin Altherma 3

Stalmine, Lancashire · Detached · 125 m² · Pre-1900 · 9 kW · underfloor · installed by Octopus Energy Services

Last 30 days

720 hourly rows · MID-class heat meter present: no
4.44efficiency (COP) over 720 hours, from the heat meter
better than 92% of the metered fleet in January 2026
Electricity used
482 kWh
Heat delivered
2138 kWh (heat meter)
Estimate without heat meter
flow sensor 4.07 · temperature model 3.88
Mean outdoor temperature
8.7 °C · 369 space-heating hours
Flow temperature at 0 °C outside
39.4 °C (curve slope -0.48 per K)
Flow − return while heating
3.7 K
House needs at −3 °C
4.1 kW (unit rated 9 kW) · fit r² 0.00
Hot water
31% of electricity, COP 3.86
warningHot water uses 31% of electricity at COP 3.86
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 9 kW but the house needs about 4.1 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day013262026-10-08: 7.3 kWh, outside 10.1 °C2026-10-09: 6.9 kWh, outside 12.1 °C2026-10-10: 11.9 kWh, outside 9.5 °C2026-10-11: 17 kWh, outside 9 °C2026-10-12: 10.2 kWh, outside 11.9 °C2026-10-13: 5.8 kWh, outside 13 °C2026-10-14: 10.4 kWh, outside 11 °C2026-10-15: 10.9 kWh, outside 12.5 °C2026-10-16: 13.1 kWh, outside 9 °C2026-10-17: 22.8 kWh, outside 5.8 °C2026-10-18: 21.2 kWh, outside 7 °C2026-10-19: 11.3 kWh, outside 9.9 °C2026-10-20: 16.5 kWh, outside 9.6 °C2026-10-21: 17.4 kWh, outside 7.6 °C2026-10-22: 12.2 kWh, outside 7 °C2026-10-23: 23.6 kWh, outside 6.4 °C2026-10-24: 17.6 kWh, outside 7.1 °C2026-10-25: 18.2 kWh, outside – °C2026-10-26: 16.7 kWh, outside 13 °C2026-10-27: 12.9 kWh, outside 10.2 °C2026-10-28: 14.2 kWh, outside 10.2 °C2026-10-29: 13.9 kWh, outside 9.2 °C2026-10-30: 16.6 kWh, outside 8.3 °C2026-10-31: 21.6 kWh, outside 6 °C2026-11-01: 25.5 kWh, outside 6.9 °C2026-11-02: 18.6 kWh, outside 5.6 °C2026-11-03: 18.7 kWh, outside 7.6 °C2026-11-04: 19.3 kWh, outside 6.9 °C2026-11-05: 19.2 kWh, outside 8.1 °C2026-11-06: 22 kWh, outside 7.7 °C2026-11-07: 8 kWh, outside 6.9 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 4.72026-10-09: COP 4.52026-10-10: COP 4.332026-10-11: COP 4.52026-10-12: COP 4.572026-10-13: COP 4.452026-10-14: COP 4.452026-10-15: COP 4.832026-10-16: COP 4.322026-10-17: COP 4.232026-10-18: COP 4.262026-10-19: COP 4.422026-10-20: COP 4.742026-10-21: COP 4.452026-10-22: COP 3.992026-10-23: COP 4.562026-10-24: COP 4.432026-10-25: COP 4.332026-10-26: COP 4.572026-10-27: COP 4.552026-10-28: COP 4.792026-10-29: COP 4.582026-10-30: COP 4.512026-10-31: COP 4.352026-11-01: COP 4.432026-11-02: COP 4.292026-11-03: COP 4.332026-11-04: COP 4.392026-11-05: COP 4.462026-11-06: COP 4.382026-11-07: COP 4.410-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
203040506013579111315outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.