Home / system #293
Daikin Altherma 3
Stalmine, Lancashire · Detached · 125 m² · Pre-1900 · 9 kW · underfloor · installed by Octopus Energy Services
Last 7 days
168 hourly rows · MID-class heat meter present: no
4.37efficiency (COP) over 168 hours, from the heat meter
better than 92% of the metered fleet in January 2026
better than 92% of the metered fleet in January 2026
- Electricity used
- 145 kWh
- Heat delivered
- 634 kWh (heat meter)
- Estimate without heat meter
- flow sensor 4.34 · temperature model 3.63
- Mean outdoor temperature
- 7.0 °C · 113 space-heating hours
- Flow temperature at 0 °C outside
- 37.5 °C (curve slope -0.18 per K)
- Flow − return while heating
- 3.8 K
- House needs at −3 °C
- 3.7 kW (unit rated 9 kW) · fit r² 0.03
- Hot water
- 27% of electricity, COP 3.81
infoUnit is rated 9 kW but the house needs about 3.7 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.