Heatproof
Home / system #625

Viessmann Vitocal 150A

Marston Moretaine · Detached · 134.61 m² · 2012 or newer · 8 kW · radiators · installed by JMR Heating and Energy

Last 30 days

717 hourly rows · MID-class heat meter present: yes
3.71efficiency (COP) over 717 hours, from the heat meter
better than 55% of the metered fleet in January 2026
Electricity used
378 kWh
Heat delivered
1403 kWh (heat meter)
Estimate without heat meter
flow sensor 3.93 · temperature model 4.44
Mean outdoor temperature
10.8 °C · 380 space-heating hours
Flow temperature at 0 °C outside
29.7 °C (curve slope 0.00 per K)
Flow − return while heating
1.1 K
House needs at −3 °C
2.5 kW (unit rated 8 kW) · fit r² 0.05
Hot water
55% of electricity, COP 3.19
warningOnly 1.1 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 55% of electricity at COP 3.19
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 8 kW but the house needs about 2.5 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day010192026-10-08: 8.1 kWh, outside 11.7 °C2026-10-09: 8.1 kWh, outside 14.7 °C2026-10-10: 7 kWh, outside 10.7 °C2026-10-11: 7.8 kWh, outside 11.4 °C2026-10-12: 5.8 kWh, outside 14.2 °C2026-10-13: 3.3 kWh, outside 15.9 °C2026-10-14: 8.6 kWh, outside 13.1 °C2026-10-15: 9.2 kWh, outside 16.8 °C2026-10-16: 10.5 kWh, outside 11.4 °C2026-10-17: 13.4 kWh, outside 8.5 °C2026-10-18: 18.5 kWh, outside 9.4 °C2026-10-19: 8.9 kWh, outside 10.9 °C2026-10-20: 13.4 kWh, outside 11.1 °C2026-10-21: 16.8 kWh, outside 8.2 °C2026-10-22: 14.4 kWh, outside 10.3 °C2026-10-23: 13.9 kWh, outside 9.9 °C2026-10-24: 14.3 kWh, outside 9.7 °C2026-10-25: 19.3 kWh, outside 10.2 °C2026-10-26: 12.4 kWh, outside 11.6 °C2026-10-27: 11 kWh, outside 13 °C2026-10-28: 14.2 kWh, outside 10.7 °C2026-10-29: 12.5 kWh, outside 11.6 °C2026-10-30: 10.5 kWh, outside 11.3 °C2026-10-31: 14.4 kWh, outside 9.4 °C2026-11-01: 16.9 kWh, outside 8.5 °C2026-11-02: 13 kWh, outside 8.8 °C2026-11-03: 16.3 kWh, outside 8.7 °C2026-11-04: 17.8 kWh, outside 8.9 °C2026-11-05: 18.1 kWh, outside 8.5 °C2026-11-06: 15.1 kWh, outside 8.7 °C2026-11-07: 4.9 kWh, outside 4.1 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 3.692026-10-09: COP 3.542026-10-10: COP 4.272026-10-11: COP 3.82026-10-12: COP 3.932026-10-13: COP 2.952026-10-14: COP 3.362026-10-15: COP 3.012026-10-16: COP 3.582026-10-17: COP 3.872026-10-18: COP 3.512026-10-19: COP 4.122026-10-20: COP 3.872026-10-21: COP 3.572026-10-22: COP 3.712026-10-23: COP 3.912026-10-24: COP 3.952026-10-25: COP 3.522026-10-26: COP 3.982026-10-27: COP 3.482026-10-28: COP 3.552026-10-29: COP 3.672026-10-30: COP 3.712026-10-31: COP 3.672026-11-01: COP 3.642026-11-02: COP 4.042026-11-03: COP 3.792026-11-04: COP 3.62026-11-05: COP 3.622026-11-06: COP 3.92026-11-07: COP 4.0810-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.