Viessmann Vitocal 150A
Marston Moretaine · Detached · 134.61 m² · 2012 or newer · 8 kW · radiators · installed by JMR Heating and Energy
Last 7 days
169 hourly rows · MID-class heat meter present: yes
3.75efficiency (COP) over 169 hours, from the heat meter
better than 59% of the metered fleet in January 2026
better than 59% of the metered fleet in January 2026
- Electricity used
- 113 kWh
- Heat delivered
- 426 kWh (heat meter)
- Estimate without heat meter
- flow sensor 3.92 · temperature model 4.07
- Mean outdoor temperature
- 8.5 °C · 112 space-heating hours
- Flow temperature at 0 °C outside
- 28.6 °C (curve slope 0.20 per K)
- Flow − return while heating
- 1.3 K
- House needs at −3 °C
- 2.3 kW (unit rated 8 kW) · fit r² 0.01
- Hot water
- 53% of electricity, COP 3.21
warningOnly 1.3 K between flow and return
Circulation pump may be set too high or emitters are undersized for the low flow temperature. Ask the installer to check pump speed.
warningHot water uses 53% of electricity at COP 3.21
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 8 kW but the house needs about 2.3 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C