Heatproof
Home / system #848

Daikin Altherma 3

South Devon · Detached · 179 m² · 1940 to 1982 · 11 kW · radiators · installed by CB Heating

5 Jan – 4 Feb 2026 (winter reference)

721 hourly rows · MID-class heat meter present: yes
3.08efficiency (COP) over 721 hours, from the heat meter
better than 12% of the metered fleet in January 2026
Electricity used
854 kWh
Heat delivered
2631 kWh (heat meter)
Estimate without heat meter
flow sensor 3.09 · temperature model 3.25
Mean outdoor temperature
6.6 °C · 448 space-heating hours · cooling 2 kWh removed (2 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
41.8 °C (curve slope -0.40 per K)
Flow − return while heating
5.3 K
House needs at −3 °C
6.9 kW (unit rated 11 kW) · fit r² 0.11
Hot water
20% of electricity, COP 2.40
infoNo configuration faults detected in this window
Keep the current settings. We will alert you if efficiency drifts.
valueReaching the fleet’s January median (3.69) would have saved about £35 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day025492026-01-05: 49.3 kWh, outside -0.3 °C2026-01-06: 42.1 kWh, outside 1.9 °C2026-01-07: 27.7 kWh, outside 5.9 °C2026-01-08: 32.2 kWh, outside 6.8 °C2026-01-09: 35.8 kWh, outside 4.7 °C2026-01-10: 38.1 kWh, outside 2 °C2026-01-11: 25.8 kWh, outside 9.2 °C2026-01-12: 16 kWh, outside 10.6 °C2026-01-13: 20 kWh, outside 9.1 °C2026-01-14: 32.8 kWh, outside 3.1 °C2026-01-15: 24.7 kWh, outside 7.1 °C2026-01-16: 28.7 kWh, outside 5.4 °C2026-01-17: 19.8 kWh, outside 6.2 °C2026-01-18: 27.8 kWh, outside 6.4 °C2026-01-19: 25.9 kWh, outside 6.4 °C2026-01-20: 32.2 kWh, outside 7.5 °C2026-01-21: 25.3 kWh, outside 8.7 °C2026-01-22: 22.4 kWh, outside 8.2 °C2026-01-23: 27.3 kWh, outside 7.9 °C2026-01-24: 29.5 kWh, outside 8.1 °C2026-01-25: 24.5 kWh, outside 7 °C2026-01-26: 28.7 kWh, outside 7.1 °C2026-01-27: 25.9 kWh, outside 8.6 °C2026-01-28: 34.2 kWh, outside 5.6 °C2026-01-29: 27.6 kWh, outside 7.6 °C2026-01-30: 26.7 kWh, outside 7.9 °C2026-01-31: 24.9 kWh, outside 7.4 °C2026-02-01: 26.1 kWh, outside 6.8 °C2026-02-02: 31.8 kWh, outside 6.4 °C2026-02-03: 20.3 kWh, outside 7.5 °C2026-02-04: 1.2 kWh, outside 7 °Cdaily COP (heat ÷ electricity)1352026-01-05: COP 2.222026-01-06: COP 2.442026-01-07: COP 2.782026-01-08: COP 3.042026-01-09: COP 2.642026-01-10: COP 2.422026-01-11: COP 3.782026-01-12: COP 3.742026-01-13: COP 3.272026-01-14: COP 2.912026-01-15: COP 3.142026-01-16: COP 2.952026-01-17: COP 2.822026-01-18: COP 3.332026-01-19: COP 2.882026-01-20: COP 3.322026-01-21: COP 3.572026-01-22: COP 3.122026-01-23: COP 3.492026-01-24: COP 3.672026-01-25: COP 2.942026-01-26: COP 3.652026-01-27: COP 3.282026-01-28: COP 2.932026-01-29: COP 3.752026-01-30: COP 3.152026-01-31: COP 2.872026-02-01: COP 2.982026-02-02: COP 3.212026-02-03: COP 3.742026-02-04: COP 4.2101-0501-0901-1301-1701-2101-2501-2902-02
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060-6-3036912outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.