Home / system #848

Daikin Altherma 3

South Devon · Detached · 179 m² · 1940 to 1982 · 11 kW · radiators · installed by CB Heating

Last 30 days

721 hourly rows · MID-class heat meter present: yes
2.96efficiency (COP) over 721 hours, from the heat meter
better than 8% of the metered fleet in January 2026
Electricity used
374 kWh
Heat delivered
1105 kWh (heat meter)
Estimate without heat meter
flow sensor 2.60 · temperature model 4.04
Mean outdoor temperature
11.7 °C · 188 space-heating hours · cooling 4 kWh removed (1 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
38.2 °C (curve slope -0.23 per K)
Flow − return while heating
3.1 K
House needs at −3 °C
6.9 kW (unit rated 11 kW) · fit r² 0.03
Hot water
25% of electricity, COP 2.32
seriousWinter efficiency 2.96 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
valueReaching the fleet’s January median (3.69) would have saved about £19 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day014272026-10-08: 3.1 kWh, outside 14.2 °C2026-10-09: 5.2 kWh, outside 15.8 °C2026-10-10: 7.8 kWh, outside 12.5 °C2026-10-11: 12.6 kWh, outside 13.3 °C2026-10-12: 3.6 kWh, outside 17.4 °C2026-10-13: 1.9 kWh, outside 16.4 °C2026-10-14: 4.4 kWh, outside 13.3 °C2026-10-15: 2.6 kWh, outside 17.3 °C2026-10-16: 5 kWh, outside 12.5 °C2026-10-17: 10.7 kWh, outside 9.7 °C2026-10-18: 12 kWh, outside 9.5 °C2026-10-19: 14.9 kWh, outside 10.6 °C2026-10-20: 13.4 kWh, outside 10.3 °C2026-10-21: 16.2 kWh, outside 10.9 °C2026-10-22: 13.3 kWh, outside 12.4 °C2026-10-23: 22.8 kWh, outside 10.8 °C2026-10-24: 13.9 kWh, outside 12.1 °C2026-10-25: 14.6 kWh, outside 11.5 °C2026-10-26: 12.7 kWh, outside 14.4 °C2026-10-27: 6.6 kWh, outside 12.8 °C2026-10-28: 11.3 kWh, outside 12.4 °C2026-10-29: 12.5 kWh, outside 11.7 °C2026-10-30: 5.2 kWh, outside 10.9 °C2026-10-31: 13.3 kWh, outside 9.5 °C2026-11-01: 15.4 kWh, outside 8.1 °C2026-11-02: 14.7 kWh, outside 10 °C2026-11-03: 18.6 kWh, outside 9.1 °C2026-11-04: 26.6 kWh, outside 8.9 °C2026-11-05: 27.4 kWh, outside 8.3 °C2026-11-06: 22.4 kWh, outside 8.5 °C2026-11-07: 10.2 kWh, outside 6.3 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 1.652026-10-09: COP 2.212026-10-10: COP 2.552026-10-11: COP 3.452026-10-12: COP 2.262026-10-13: COP 1.252026-10-14: COP 1.832026-10-15: COP 2.392026-10-16: COP 1.882026-10-17: COP 2.472026-10-18: COP 2.462026-10-19: COP 3.142026-10-20: COP 3.052026-10-21: COP 3.092026-10-22: COP 3.052026-10-23: COP 3.262026-10-24: COP 3.592026-10-25: COP 2.782026-10-26: COP 4.042026-10-27: COP 2.62026-10-28: COP 3.022026-10-29: COP 3.362026-10-30: COP 2.852026-10-31: COP 2.992026-11-01: COP 2.832026-11-02: COP 2.852026-11-03: COP 2.742026-11-04: COP 3.112026-11-05: COP 3.032026-11-06: COP 2.82026-11-07: COP 2.4510-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
2030405060246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.