Daikin Altherma 3
South Devon · Detached · 179 m² · 1940 to 1982 · 11 kW · radiators · installed by CB Heating
Last 7 days
169 hourly rows · MID-class heat meter present: yes
2.92efficiency (COP) over 169 hours, from the heat meter
better than 7% of the metered fleet in January 2026
better than 7% of the metered fleet in January 2026
- Electricity used
- 146 kWh
- Heat delivered
- 425 kWh (heat meter)
- Estimate without heat meter
- flow sensor 2.43 · temperature model 3.66
- Mean outdoor temperature
- 8.9 °C · 76 space-heating hours · cooling 3 kWh removed (1 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 36.6 °C (curve slope 0.03 per K)
- Flow − return while heating
- 3.0 K
- House needs at −3 °C
- 5.9 kW (unit rated 11 kW) · fit r² 0.00
- Hot water
- 17% of electricity, COP 2.23
seriousWinter efficiency 2.92 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
valueReaching the fleet’s January median (3.69) would have saved about £8 in this window at 0.25 GBP/kWh. An estimate, not a promise.