Daikin Altherma 3
Stratford-upon-Avon, West Midlands · Mid-terrace · 153 m² · Pre-1900 · 16 kW · radiators · installed by BUTCO Heating Ltd
1–31 Dec 2025
418 hourly rows · MID-class heat meter present: yes
2.20efficiency (COP) over 418 hours, from the heat meter
better than 1% of the metered fleet in January 2026
better than 1% of the metered fleet in January 2026
- Electricity used
- 761 kWh
- Heat delivered
- 1672 kWh (heat meter)
- Estimate without heat meter
- flow sensor 2.15 · temperature model 3.21
- Mean outdoor temperature
- 6.1 °C · 229 space-heating hours · cooling 5 kWh removed (2 kWh electricity), kept out of the COP
- Flow temperature at 0 °C outside
- 38.8 °C (curve slope -0.24 per K)
- Flow − return while heating
- 4.2 K
- House needs at −3 °C
- 7.2 kW (unit rated 16 kW) · fit r² 0.19
- Hot water
- 35% of electricity, COP 2.10
seriousWinter efficiency 2.2 is below the 3.0 floor used for German subsidies
Ask the installer for a commissioning check; the causes are usually flow temperature, hot water settings, or sizing, all listed below.
warningHot water uses 35% of electricity at COP 2.1
Lower the tank target to 45–48 °C, heat water once a day in the warmest hours, and disable weekly legionella cycles unless required.
infoUnit is rated 16 kW but the house needs about 7.2 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £77 in this window at 0.25 GBP/kWh. An estimate, not a promise.
Day by day
electricity per daydaily COP3.0 floor
The installed heating curve
one heating hourfitted curve50 °C
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.