Daikin Altherma 3

Stratford-upon-Avon, West Midlands · Mid-terrace · 153 m² · Pre-1900 · 16 kW · radiators · installed by BUTCO Heating Ltd

Last 30 days

721 hourly rows · MID-class heat meter present: yes
3.55efficiency (COP) over 721 hours, from the heat meter
better than 40% of the metered fleet in January 2026
Electricity used
450 kWh
Heat delivered
1595 kWh (heat meter)
Estimate without heat meter
flow sensor 3.32 · temperature model 4.42
Mean outdoor temperature
10.8 °C · 242 space-heating hours · cooling 4 kWh removed (4 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
40.5 °C (curve slope -0.36 per K)
Flow − return while heating
4.6 K
House needs at −3 °C
6.9 kW (unit rated 16 kW) · fit r² 0.05
Hot water
24% of electricity, COP 3.02
infoUnit is rated 16 kW but the house needs about 6.9 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £4 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day011232026-10-08: 4.8 kWh, outside 12.5 °C2026-10-09: 9.7 kWh, outside 14.9 °C2026-10-10: 15.5 kWh, outside 11.3 °C2026-10-11: 7.5 kWh, outside 11.1 °C2026-10-12: 11 kWh, outside 15.7 °C2026-10-13: 4.7 kWh, outside 15.9 °C2026-10-14: 11.4 kWh, outside 13.7 °C2026-10-15: 7.2 kWh, outside 17 °C2026-10-16: 11.4 kWh, outside 10.7 °C2026-10-17: 19 kWh, outside 7.3 °C2026-10-18: 19.1 kWh, outside 9.4 °C2026-10-19: 15.7 kWh, outside 10.4 °C2026-10-20: 16.4 kWh, outside 10.2 °C2026-10-21: 22.4 kWh, outside 8.6 °C2026-10-22: 16.1 kWh, outside 10.3 °C2026-10-23: 21.5 kWh, outside 9.5 °C2026-10-24: 19 kWh, outside 10 °C2026-10-25: 18.3 kWh, outside 10.6 °C2026-10-26: 14.8 kWh, outside 12.3 °C2026-10-27: 9.9 kWh, outside 13 °C2026-10-28: 13.9 kWh, outside 11 °C2026-10-29: 11.9 kWh, outside 11.4 °C2026-10-30: 9.2 kWh, outside 10.7 °C2026-10-31: 15.6 kWh, outside 8.9 °C2026-11-01: 19.3 kWh, outside 8.5 °C2026-11-02: 21.5 kWh, outside 8 °C2026-11-03: 20.6 kWh, outside 7.5 °C2026-11-04: 18.9 kWh, outside 9.3 °C2026-11-05: 22.7 kWh, outside 8.7 °C2026-11-06: 21.6 kWh, outside 8.8 °C2026-11-07: 2.8 kWh, outside 4.6 °Cdaily COP (heat ÷ electricity)1352026-10-08: COP 3.222026-10-09: COP 3.762026-10-10: COP 3.692026-10-11: COP 2.322026-10-12: COP 4.032026-10-13: COP 1.732026-10-14: COP 3.492026-10-15: COP 2.752026-10-16: COP 3.392026-10-17: COP 3.272026-10-18: COP 3.212026-10-19: COP 3.632026-10-20: COP 3.742026-10-21: COP 3.632026-10-22: COP 3.542026-10-23: COP 3.722026-10-24: COP 3.712026-10-25: COP 3.572026-10-26: COP 3.882026-10-27: COP 3.692026-10-28: COP 3.922026-10-29: COP 3.782026-10-30: COP 3.262026-10-31: COP 3.612026-11-01: COP 3.382026-11-02: COP 3.342026-11-03: COP 3.482026-11-04: COP 3.642026-11-05: COP 3.52026-11-06: COP 3.532026-11-07: COP 1.9410-0810-1210-1610-2010-2410-2811-0111-05
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050600246810121416outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.