Home / system #931

Daikin Altherma 3

Stratford-upon-Avon, West Midlands · Mid-terrace · 153 m² · Pre-1900 · 16 kW · radiators · installed by BUTCO Heating Ltd

Last 7 days

169 hourly rows · MID-class heat meter present: yes
3.49efficiency (COP) over 169 hours, from the heat meter
better than 37% of the metered fleet in January 2026
Electricity used
137 kWh
Heat delivered
479 kWh (heat meter)
Estimate without heat meter
flow sensor 3.20 · temperature model 3.73
Mean outdoor temperature
8.4 °C · 81 space-heating hours · cooling 1 kWh removed (1 kWh electricity), kept out of the COP
Flow temperature at 0 °C outside
41.4 °C (curve slope -0.43 per K)
Flow − return while heating
4.7 K
House needs at −3 °C
7.6 kW (unit rated 16 kW) · fit r² 0.07
Hot water
16% of electricity, COP 2.60
infoUnit is rated 16 kW but the house needs about 7.6 kW at −3 °C
Oversizing causes cycling in mild weather. Cannot be fixed cheaply now, but the curve and minimum run time can limit the damage.
valueReaching the fleet’s January median (3.69) would have saved about £2 in this window at 0.25 GBP/kWh. An estimate, not a promise.

Day by day

electricity per daydaily COP3.0 floor
electricity, kWh per day011232026-10-31: 10.5 kWh, outside 9.6 °C2026-11-01: 19.3 kWh, outside 8.5 °C2026-11-02: 21.5 kWh, outside 8 °C2026-11-03: 20.6 kWh, outside 7.5 °C2026-11-04: 18.9 kWh, outside 9.3 °C2026-11-05: 22.7 kWh, outside 8.7 °C2026-11-06: 21.6 kWh, outside 8.8 °C2026-11-07: 2.8 kWh, outside 4.6 °Cdaily COP (heat ÷ electricity)1352026-10-31: COP 3.782026-11-01: COP 3.382026-11-02: COP 3.342026-11-03: COP 3.482026-11-04: COP 3.642026-11-05: COP 3.52026-11-06: COP 3.532026-11-07: COP 1.9410-3111-0111-0211-0311-0411-0511-0611-07
Daily COP needs a heat meter; days without one show electricity only.

The installed heating curve

one heating hourfitted curve50 °C
20304050602468101214outdoor temperature, °Cflow temperature, °C
Each point is one hour of space heating. Lower and flatter is cheaper; well-set radiator systems sit around 35–42 °C at 0 °C outside.
Public system published by its owner on HeatpumpMonitor.org. Cycling (starts per hour) comes from the site’s 365-day statistic. Findings use installer rules of thumb; see methodology.